Electrical heating system is used in various industries to protect the freezing of pipes (such as gas) or to maintain fluid temperature inside the pipes or reservoirs.
The maximum temperature can be tolerated by the heating cable when it’s on. Therefore, if the surface temperature reaches this temperature, it’s needed to be cut off the circuit by the temperature controller and heating cable exit from the circuit.
The maximum temperature at which the heating cable can stand in no charge (off) condition. Therefore, installing the cable on a surface that may have a temperature higher than the POWER OFF temperature is totally unauthorized.
HEAT-TRACE heating cables have this feature, which has the same two parameters, thus increasing the life of the cable and reducing the cost of the project due to no need for the thermostat to cut off the current at POWER ON temperature.Steam Tracing Historically, steam tracing has been used more often than any other type of pipeline heating, for freeze protection and for process heating. Steam typically has an advantage of having a high heat capacity combined with a suitable heat transfer coefficient. This high heat input has been advantageous in the past because thermal insulation systems on pipelines were often left for years without maintenance. When energy costs were negligible, this was an acceptable method of operation, since steam was perceived as being “free of costs”. When flowing through a tube, the steam will dissipate its latent heat to the process pipe to compensate for the loss in heat. During this process the steam temperature remains constant.
However when all steam condenses, the tube will then be filled with condensate which has a significantly lower heat capacity and a worse heat transfer coefficient. This process occurs gradually and along the entire length of the heating tube. Therefore it is necessary to install a steam trap at the end of the heating circuit to "trap the steam" and discharge the condensate with a minimum loss of fresh steam. Because the condensate in the heating tube has to be "pushed" to the steam trap (often upwards), the steam system must have sufficient pressure, which limits the maximum length of the heating circuits. Circuits which are too long will "drown" in condensate and the heat transfer will become very unpredictable and unstable, which adds complexity to the steam tracing system. The inherent result of the short heat tracing circuits is that valuable space in the process area is used for the steam distribution and condensate collection infrastructure. Steam traps are the most critical and at the same time most sensitive component of the steam tracing system. Due to the mechanical nature of the steam system with constantly moving parts often resulting in abrasion by the steam and blockage because of poor steam quality; steam traps are subject to frequent inspections (at least once annually) to ensure continued operation of which a significant number of the traps (roughly 6%) must be replaced each year. Energy waste is often high on steam-tracing systems. Steam being a constant temperature source, any non-flowing pipeline is elevated to the temperature of the steam-tracing circuit over a period of time. On flowing pipelines the steam will continually transfer energy to the fluid at a higher rate because the temperature differential between the steam and the fluid essentially stays constant. Both conditions provide more heat energy to the system than is required to maintain design conditions. To date, there is no reliable method for controlling the pipeline temperature and energy usage. Depending on the type of steam trap used; even under perfect working conditions, there will always be some loss of steam. If the traps fail-open, there will be a significant amount of steam loss especially because these systems are in operation 24/7. A brief technical differentiation between steam and electric heat tracing (mineral insulated) is provided in the table below.
Typically, an electric heat tracing system is approximately 75% of the total installed cost of a steam tracing system, when taking into account the tracing system, the control & monitoring, and the power distribution system.
The total installed cost will vary according to location and specific heat-input requirements, but remain constant as an industry average. Heat Tracing Solutions can perform a complete technical and economic analysis on a customer’s heat tracing system to determine the best value for that specific application.
From a safety perspective, there is a much higher probability of the potential for maintenance personnel to be susceptible to burns while working on and around steam-traced systems due to the exposed valves and traps. Electric heat tracing on the other hand, is intrinsically safe since it has no exposed circuits and also has ground fault protection.
Electrical heating systems can include a wide variety of control and monitoring products, from simple mechanical thermostats and signal lights to sophisticated multi-circuit digital controllers. These control products vary the output of the heating source to keep pipes from freezing or to maintain process piping at elevated temperatures. From a maintenance perspective, with the electric heating system, most maintenance can be based on results from control and monitoring incorporated into the design of the system itself.
Steam-tracing systems, on the other hand, do not offer any reasonable form of control and monitoring. The largest maintenance items in a steam tracing system are the steam traps, as they are typically the items which are most likely to fail during operation. The documented service life of a typical steam trap is three years, with a minimum replacement cost of approximately $95. As a result, it is also recognized that the maintenance of the condensate return is always higher than that of the steam supply, as the liquid and steam cause erosion of the elbows in the system. This is why many condensate return systems are constructed of stainless steel.
The chart shown below provides an example of where the maintenance costs of the electrical heat-tracing and steam-tracing systems are compared for a process maintenance heating application.
a. INDUSTRIAL
b. COMMERCIAL
The application of heating cable to pipe work/plant carrying water or aqueous based solutions to prevent freezing
The application of heating cables to pipework and plant to maintain their contents at a specific temperature above the lowest expected ambient conditions
The application of heating cables to pipe work and plant to raise the pipe and contents from a low start-up temperature to a specific maintain temperature above the lowest expected ambient conditions within an agreed period of time. This may also include a change of state of product or may be required under flow conditions.
The components of the electrical heating system include Heath tracing cable with installation, control and monitoring equipment and implementation of an appropriate insulation coating is essential to maintain the temperature and proper system operation.
The heating system cables in terms of energy production are in 2 types of self-regulation and constant power, which are selected regarding to design and use.
Semi conductive parallel resistance heating cables mainly for use in freeze protection or temperature maintenance applications. Approved for use in both safe and hazardous areas. For use up to 300°C (572°F).We can produce self-regulating heating cables within the following ranges:
Low Temperature
FREEZSTOP MICRO
FSM withstand tempraturas - 65°C
energised / 85°C un-enegised.
FREEZSTOP LITE
FSLe withstand tempratures - 85°C
energised / 85°C un-enegised.
FREEZSTOP REGULAR
FSR withstand tempratures - 85°C
energised / 85°C un-enegised.
FREEZSTOP EXTRA
FSE withstand tempratures - 100°C
energised / 100°C un-enegised.
CONDUCTOR RAIL HEATER
CRH maximum tempratures
135°C un-enegised./ minimum installation temperature -40°C
FREEZ STOP LOW VOLTAGE
FLV maximum exposure temperature
85°C energised
maximum exposura
temperature 85°C
G-TRACE
GT ambient temperature
range +60°C to -40°C
High Temperature
FAILSAFE +
FS+ withstand temperatures - 225°C
energised / 225°C un-enegised.
FAILSAFE SUPER
FSS withstand temperatures - 225°C
energised / 225°C un-enegised
FAILSAFE ULTIMO
FSU withstand temperatures - 250°C
energised / 250°C un-
enegised.
Very High Temperature
FAILSAFE ULTIMO+
FSU+ withstand temperatures - 275°C
energised / 275° un-enegised.
AUTO FAILSAFE
AFS withstand temperatures - 300°C
energised / 300°C un-enegised.
(reduced to 275°C when
overjacket is provided).
Constant Wattage heating cables (zonal heating cables) can be conveniently cut-to-length, but are less popular than self-regulating heating cables, because they often require thermostatic control to ensure temperature safety.Suitable for use in both safe and hazardous areas. We can produce constant wattage heating cables within the following ranges:
Low and Medium Temperature
MICROTRACER
Withstand Temperature up to 200°C
MINITRACER
Withstand Temperature up to 200°C
Mineral High Temperature
MINERAL INSULATED - MAL
Withstand Temperature up to 800°C
High Temperature
POWERHEAT - PHT
Withstand Temperature up to 285°C
POWERHEAT - RHT / RHT / U
Withstand Temperature up to 425°C
POWERHEAT - AHT
Withstand Temperature up to 500°C
Series Resistance heating cables have to be individually designed into particular length and load configurations and so are not as versatile as parallel cables. Suitable for use in both safe and hazardous areas. We can produce series resistance heating cables within the following ranges:
Low Temperature
LONGLINE - HTP3F
Withstand Temperature up to 125°C
LONGLINE - HTP1F
Withstand Temperature up to 125°C
Medium Temperature
LONGLINE - HTS3F
Withstand Temperature up to 230°C
LONGLINE - HTS1F
Withstand Temperature up to 230°C
B. Termination and Installation Components
B.1. Terminations - power end
Direct Entry Sealed Termination Unit (DESTU)
This is an improved method, where the j unction box is connected to the DESTU, which is mounted onto the pipe surface. The tracer passes through the DESTU into the junction box, avoiding the possibility of damage to the tracer where it exits the thermal insulation.
Strip Free Unit (SF/T or SF/P)
The Strip Free connection box has been specially developed by Heat Trace to reduce installation time and component costs. Tracers can be terminated without the need to strip the ends of self-regulating tracers. Strip Free units are available for connection to the power supply and also for series and tee connections. Strip Free boxes are particularly useful for small diameter instrument lines which cannot support large junction boxes.
Standard Method
This uses tracer termination gland components and a junction box. To avoid the possibility of damage to the tracer where it exits from the thermal insulation, a separate lagging entry kit is required.
B.2. Terminations - remote end
Moulden end seal
The silicone rubber end seal is fixed with an adhesive. It is a simple and low cost form of sealing.
Strip Free End seal (SF/E)
The silicone rubber end seal is fixed with an adhesive. It is a simple and low cost form of sealing.
Heat Shrink seal
The silicone rubber end seal is fixed with an adhesive. It is a simple and low cost form of sealing.
Termination Components & Respective Heating Cables
A range of miscellaneous components for use when installing Heat Trace products:
A range of adhesive and non-adhesive fixing methods for securing heating cable in position:
Selection Guide
Type I process control - maintaining above a minimum temperature level
Type II process control - maintaining within a broad temperature band
Type III process control - maintaining within a narrow temperature band
Heat Trace takes and active part in the development and implementation of electric heat tracing industry standards.
Heat Trace’s products conform to several International Standards, some of which are shown below:
Step2. Determine Heat Losses
In order to determine the correct heating tape or cable according to the application the following information will be necessary
Step 3.1: Select Heating Cable Family
Step 3.2: Select Heating Cable Construction Options
Step 3.3: Select Thermal Output Rating
Step 3.4: Check T-Ratings
Step 3.5: Select Voltage Rating and Adjust for Alternate Voltages
Step 3.6: Determine Heat-Trace Part Number
Step 3.1: Select Heating Cable Family
Step 3.2: Select Heating Cable Construction Options
Pipe length of 50 m single pass application
2 Butterfly Valves, additional cable 0.6 m each valve
10 Pipe Shoe Supports, additional cable per support is 0.6 m
= 50m 45FS+2-CF
=1.2m 45FS+2-CF
= 6m 45FS+2-CF